Three-phase voltages are 120° apart, not 180°. If the three voltages are drawn 120° apart, it will be seen that the vector sum of these voltages is 208 V.
Delta connection
Here we have three separate inductive loads that have been connected to form a delta connection. This connection receives its name from the fact that a schematic diagram of this connection resembles the Greek letter delta (Δ). Voltmeters have been connected across the lines and across the phase. Ammeters have been connected in the line and in the phase. In the delta connection, line voltage and phase voltage are the same. The line current and phase current are different, however. The line current of a delta connection is higher than the phase current by a factor of the square root of 3 (1.732).
In the above example it is assumed that each of the phase windings has a current flow of 10 A. The current in each of the lines, however, is 17.32 A. The reason for this difference in current is that current flows through different windings at different times in a three-phase circuit. During some periods of time, current will flow between two lines only. At other times, current will flow from two lines to the third.
The delta connection is similar to a parallel connection because there is always more than one path for current flow. Since these currents are 120° out of phase with each other, vector addition must be used when finding the sum of the currents.
Three-phase power
An apparent power calculation (VA) represents the total electrical capacity of a system. A three-phase system is quite literally a combination of three separate single-phase systems working together. If we look inside any three-phase generator, motor, or transformer, we will find three distinct electrical windings (phases). The true, total power of the system is always the sum of the power being produced or consumed by each of those three individual phases:
Total VA = Phase 1 Power + Phase 2 Power + Phase 3 Power
There are actually two formulas that can be used when calculating three-phase power.
If the phase values of voltage and current are known, the apparent power can be computed using the formula:
VA = 3 x Ephase x Iphase
While the phase formula makes perfect sense theoretically, it is often impractical in the real world. Windings are usually sealed deep inside motor casings or transformer tanks. Electricians cannot easily hook up a voltmeter or clamp-on ammeter around an internal phase winding.
Instead, they measure the external line wires coming out of the machine. To make use of these line measurements, we must substitute them into our core formula using the geometric rules of Wye (Ephase = Eline/√3, Iphase = Iline) and Delta (Iphase = Iline/√3, Ephase = Eline) configurations.
If line values of voltage and current are known, the power can be computed using the formula:
VA = √3 x Eline x Iline
So, both formulas give the same result, Wye or Delta. In the first formula, the phase values of voltage and current are multiplied by 3. In the second formula, the line values of voltage and current are multiplied by the square root of 3. The second formula is used more often because it is generally more convenient to obtain line values of voltage and current, which can be measured with a voltmeter and clamp-on ammeter.
This is the total apparent power of the system. It represents the maximum capacity required of the electrical infrastructure (conductors, transformers and switchgear).
True or active power is the actual power that performs useful physical work, such as turning a motor shaft, pumping water, or generating heat. It accounts for the Power Factor (PF), which is mathematically equal to the cosine of the phase shift angle (cosθ).
Line formula: P = √3 x Eline x Iline x PF
Phase formula: P = 3 x Ephase x Iphase x PF
Reactive power is the non-working power that sloshes back and forth between the source and the load. It is used to sustain the alternating magnetic fields required by inductive loads (like motor windings or magnets). It uses the sine of the phase shift angle (sinθ).
Line formula: Q = √3 x Eline x Iline x sinθ
Phase formula: Q = 3 x Ephase x Iphase x sinθ
The Power Triangle:
S = √(P2 + Q2)
These three components form a right-angled triangle where Apparent Power (S) is the hypotenuse, True Power (P) is the adjacent side, and Reactive Power (Q) is the opposite side.
For an unbalanced system, we cannot use √3 shortcut; instead we must:
1. Measure the voltage and current for each phase independently.
2. Calculate the active power (P) and reactive power (Q) for each phase separately, i.e. P1 = U1I1cosΘ1, P2 = U2I2cosΘ2, etc.
3. Sum the individual phases:
Ptotal = P1+P2+P3
Qtotal = Q1+Q2+Q3
4. Find the true total apparent power vectorially: VAtotal = √(Ptotal2 + Qtotal2).
High-end digital power meters and power analyzers do not use the simple √3 formula; they continuously sample the voltage and current of all three phases individually and sum them up, which is why they remain accurate even when a load is heavily unbalanced.
Example:
A wye-connected three-phase alternator supplies power to a delta-connected resistive load, shown on the figure below. The alternator has a line voltage of 480 V. Each resistor of the delta load has 8 Ω of resistance. Calculate another circuit values...
Solution:
The load is connected directly to the alternator. Therefore, the line voltage supplied by the alternator is the line voltage of the load.
EL(load) = 480 V
The three resistors of the load are connected in a delta connection. In a delta connection, the phase voltage is the same as the line voltage.
EP(load) = EL(load)
EP(load) = 480 V
Each of the three resistors in the load is one phase of the load. Now that the phase voltage is known, the amount of phase current can be computed using Ohm’s Law.
IP(load) = EP(load)/Z
IP(load) = 480/8 = 60 A
The three load resistors are connected as a delta with 60 A of current flow in each phase. The line current supplying a delta connection must be 1.732 times greater than the phase current.
IL(load) = √3 x IP(load)
IL(load) = 1.732 x 60 = 103.92 A
The alternator must supply the line current to the load or loads to which it is connected. In this example, only one load is connected to the alternator. Therefore, the line current of the load will be the same as the line current of the alternator.
IL(alt) = IL(load)
IL(alt) = 103.92 A
The phase windings of the alternator are connected in a wye connection. In a wye connection, the phase current and line current are equal. The phase current of the alternator will, therefore, be the same as the alternator line current.
IP(alt) = IL(alt)
IP(alt) = 103.92 A
The phase voltage of a wye connection is less than the line voltage by a factor of the square root of 3.
EP(alt) = EL(alt)/√3
EP(alt) = 480/√3 = 277.13 V
In this circuit, the load is pure resistive. The voltage and current are in phase with each other, which produces a unity power factor of 1. The true power in this circuit is:
P = √3 x EL(alt) x IL(alt) x PF
P = 1.732 x 480 x 103.92 x 1 = 86,394.93 W